Carbon Dioxide Fire Suppression System - Essay casefulFor carbon dioxide to be effective as a total flooding fire suppressant, a borderline design of 34% concentration is needed. However, laboratory testing and simulation of carbon dioxide fire suppressant ingestion indicate that concentrations greater than 17% results to loss of controlled and purposeful activity, convulsions, unconsciousness, coma and even death within 1 minute of initial inhalation (OSHA, 1999).Even at 10-17% concentrations, carbon dioxide inhalation has been shown by Wong (1992) to result to drowsiness, resolve muscle twitching and even unconsciousness. At 7 to 10 percent, headaches, visual and hearing dysfunction, hallucination and curtness of breath have been observed. At a minimum of 34% designed concentration for effectiveness, Carbon dioxide quelling systems are lethal. Any inadvertent discharge of the carbon dioxide in an occupied room can take a leak death quickly and without warning.The National Fi re Protection Agency and the Occupational Safety and Health authorization have established guidelines such that human exposure do not occur during fire-fighting events but documented cases occurred during system installation, commissioning and maintenance because many of the servicemen lack the necessary knowledge and training.OSHA (1999) Carbon Dioxide, Industrial picture show and Control Technologies for OSHA Regulated Hazardou